Why won’t Pactware work with the Siemens LUT 400?
Posted by danstips in Configuration, Flow, Flowmeters, Level, Level Technology, Siemens, Software, Troubleshooting, Ultrasonic, Ultrasonic Flowmeters, Wireless, WirelessHART on October 22, 2015
Written by: Dan Weise
I’ve used Pactware for a couple years now, so I was surprised when I couldn’t get the Siemens LUT400 to work with the software. The LUT400 ultrasonic level and flow controller comes with a DTM file that I installed before opening the Pactware software.
The DTM file can be downloaded from this link: http://tinyurl.com/cqk2cky
Once it had been installed, I opened Pactware and updated the device catalog, as seen in the picture below:
But when I attempted to establish a HART connection to the LUT400, I got an error message:
LUT400 universal 4-20mA analog output gets rid of the ground loop
Posted by danweise in 4-20mA, HART, Installation, Level, Level Transmitters, Ultrasonic on August 16, 2013
The Problem
Before I talk about the value of a universal 4-20mA analog output on a level controller, let me explain why anyone would care. It’s all about ground loops.
Since the early days of electronic instrumentation, way back when, even before cell phones or PCs, instrument people struggled with ground loops that create an offset error, drive the signal off scale, or burn up an analog circuit.