Changing the Clock Battery on a Honeywell Paperless Recorder
Posted by danstips in Honeywell, Paperless Recorders, Trendview X-Series Paperless Recorders, Troubleshooting on April 14, 2016
Written by: Dan Weise
The installed base of Honeywell Trendview X series paperless recorders is approaching an in-service period of a decade (introduced mid-2006). Given that kind of service time, you need to be aware of the issues involved in changing the clock battery.
The replaceable clock battery serves as a backup for the on board real-time clock chip as well as the internal battery-backed static RAM. If your paperless recorder is getting old, the battery may ready for a swap-out. If so, you may need a one-day-use access code that only Honeywell can provide, so plan ahead. You don’t want to get locked out of your recorder!
Honeywell Increases Analog/Loop Processing Speed on HC900 Process and Safety Controller
Posted by danstips in Control, Honeywell, Process Automation Controllers, Safety Control on April 6, 2016
Written by: Dan Weise
Good news! Recent upgrades to Honeywell’s HC900 Process and Safety Controller includes a major update to analog/loop processing speeds. Even though analog/loop cycle time has been 500mS since the early 2000s, early versions of the HC900 controller were only capable of a processing speed of 2x/second.
The upgrade to the HC900 CPU’s microprocessor hardware and an associated firmware update broke that processing speed limit for their SIL-rated CPUs. Honeywell C50S and C70S model CPUs v6.1 will now process analog inputs and loops at a rate of 10x/second (100mS per update). If your process needs additional analog/loop throughput speed, you will benefit from these enhancements to the HC900 systems.
To run at 100mS, a qualified hardware configuration is required: